Danfoss Thermostat LC
From MiOS
(Difference between revisions)
(→Wakeup interval) |
m (→Power consumption) |
||
| (3 intermediate revisions by one user not shown) | |||
| Line 115: | Line 115: | ||
| No | | No | ||
| 3 | | 3 | ||
| − | | 1.5.622, Z-Wave version 3.20 | + | | 1.5.622, Z-Wave version 3.20, Vera routing |
| [[File:Danfoss_LC_SW1.00.jpg|100px]] | | [[File:Danfoss_LC_SW1.00.jpg|100px]] | ||
| − | | under test | + | | excellent performance; power consumption still under test |
|} | |} | ||
| − | |||
== Test results for Danfoss LC Z (014G0013, firmware version 1.00, wakeup interval 300 seconds; MiOS 1.5.622, Z-Wave version 3.20, Vera routing instead of Z-Wave)== | == Test results for Danfoss LC Z (014G0013, firmware version 1.00, wakeup interval 300 seconds; MiOS 1.5.622, Z-Wave version 3.20, Vera routing instead of Z-Wave)== | ||
| Line 134: | Line 133: | ||
===Reaction time=== | ===Reaction time=== | ||
| + | |||
| + | Left vertical scale: CurrentSetpoint, CurrentTemperature | ||
| + | |||
| + | Right vertical scale: SetpointTarget | ||
| + | |||
| + | Temperature sensor near thermostat. | ||
| + | |||
| + | [[File:Danfoss_SZ_Reaction_Time.jpg|600px]] | ||
| + | |||
| + | Excellent reaction time (within one wakeup interval). | ||
===Power consumption=== | ===Power consumption=== | ||
| + | |||
| + | Using Sony batteries supplied with the thermostats. | ||
| + | |||
| + | [[File:Danfoss_bl_2_months.jpg|600px]] | ||
| + | |||
| + | Some abnormalities (non-monotonically decreasing battery levels; high drop on February, 27th; 100% spike). | ||
== Checking the wakeup interval == | == Checking the wakeup interval == | ||
Latest revision as of 12:49, 20 April 2014
Please note that LC firmware revision 3.02 is not compatible with Z-Wave.
Contents |
[edit] HW revisions
| Part no. | Firmware | Z-Wave version | Capabilities | Z-Wave classes | extra menu options | Vera | MiOS | Photo | Issues | |
|---|---|---|---|---|---|---|---|---|---|---|
| 014G0009 | 1.06 | delay issueunreliable | ||||||||
| 014G0002, 014G0009 | 2.06 | 6,2,67,2,6 | 81,140,0,4,8,4,R,RS | 67,70,114,117,128,129,132:2,134,143,145, | No | V2 | 1.5.408 | |
? | |
| 2.06 | Lite | 1.5.408 | no issues | |||||||
| 2.06 | 3 | 1.5.459 | no issues | |||||||
| 014G0012 | 2.50 | Lite | 1.5.408 | no issues | ||||||
| 014G0012 | 2.51 | 6,2,67,2,51 | 81,140,0,4,8,4,R,RS | 67,70,114,117,128,129,132:2,134,143, | 2 | 1.5.408 | photo | no issues | ||
| 014G0012 | 2.5.3 | Lite | 1.5.408 | no issues | ||||||
| 014G0002 | 3.02 | 0x72, 0x91 only(?) | not compatible | |||||||
| 014G0013 | 1.00 | 6,3,67,1,0 | 83,156,0,4,8,4,R,B,RS | 67,70,114,117,128,129,132:2,134,143 | No | 3 | 1.5.622, Z-Wave version 3.20, Vera routing | |
excellent performance; power consumption still under test |
[edit] Test results for Danfoss LC Z (014G0013, firmware version 1.00, wakeup interval 300 seconds; MiOS 1.5.622, Z-Wave version 3.20, Vera routing instead of Z-Wave)
[edit] Wakeup interval
Excellent Wakeup performance. Non-equidistant points (B_Danfoss) due to manual operation.
[edit] Reaction time
Left vertical scale: CurrentSetpoint, CurrentTemperature
Right vertical scale: SetpointTarget
Temperature sensor near thermostat.
Excellent reaction time (within one wakeup interval).
[edit] Power consumption
Using Sony batteries supplied with the thermostats.
Some abnormalities (non-monotonically decreasing battery levels; high drop on February, 27th; 100% spike).
[edit] Checking the wakeup interval
local danfoss_devices = { { 221, 'KiZ' },
{ 218, 'B' },
{ 211, 'SZ' },
{ 107, 'WZS' },
{ 94, 'WZN' } }
function log_wakeup( lul_device, lul_service, lul_variable, lul_value_old, lul_value_new )
local s = ''
for i = 1,#danfoss_devices
do
if danfoss_devices[ i ][ 1 ] == tonumber( lul_device )
then
s = danfoss_devices[ i ][ 2 ]
end
end
os.execute( 'logger -t Heizung Wakeup_' .. s )
end
for i = 1,#danfoss_devices
do
luup.variable_watch( 'log_wakeup', 'urn:micasaverde-com:serviceId:ZWaveDevice1', 'LastWakeup', danfoss_devices[ i ][ 1 ] )
end[edit] Synchronizing the Danfoss GUI device with temperature sensors
... using a TFA 30.3133 temperature sensor (ironically, MiOS doesn't support decidegrees for Z-Wave temperature sensors).
-- list of { temperature_sensor_device_id, { list of Danfoss_LC_device_id } }
devices_to_synchronize = { { 167, { 218 } }, -- B
{ 162, { 221 } }, -- KiZ
{ 169, { 211 } }, -- SZ
{ 170, { 94, 107 } } } -- WZS, WZN
function synchronize_temp( lul_device, lul_service, lul_variable, lul_value_old, lul_value_new )
for i = 1,#devices_to_synchronize
do
if devices_to_synchronize[ i ][ 1 ] == tonumber( lul_device )
then
for j = 1,#devices_to_synchronize[ i ][ 2 ]
do
luup.variable_set( 'urn:upnp-org:serviceId:TemperatureSensor1', 'CurrentTemperature', lul_value_new, devices_to_synchronize[ i ][ 2 ][ j ] )
end
end
end
end -- synchronize_temp
for i = 1,#devices_to_synchronize
do
luup.variable_watch( 'synchronize_temp', 'urn:upnp-org:serviceId:TemperatureSensor1', 'CurrentTemperature', devices_to_synchronize[ i ][ 1 ] )
end